Call Us! 800-627-4499

HE1XINH

  • icon Summary
  • icon Options
  • icon Drawings
  • icon Literature
  • icon Accessories
HE1XINH

Overview

  • Indoor Fan Powered Packaged Energy Recovery Ventilator
  • Typical Airflow Range: 250-925 cfm
  • AHRI 1060 Certified Core - One L125-G5
  • Direct drive 0.75 hp motors (2)
  • Quiet, forward curve blowers (2)
  • Available in single or three phase with multiple voltage options
  • Horizontal airflow orientation

Key Features

  • Utilizes RenewAire's exceptional static plate energy exchange core
    • AHRI certified performance data for efficiency and cross leakage
    • Ten year core performance warranty
    • Suitable for restroom exhaust
  • No liquid water (condensate) or accompanying drain line to deal with - as with many competing brands
  • No mounting restrictions - mount overhead, against a wall - vertical or horizontally
  • Access doors can be completely and easily removed allowing complete access to all internal components
  • Two separate access doors, one for the core, the other for the blower compartment
  • Built-in pressure ports with captive plugs allowing cross-core pressure measurement and accurate airflow measurement
  • One inch thick dense fiberboard insulation with scrimmed foil facing - washable, durable and easy to maintain - no loose insulation fibers to break off and enter the airstreams
  • Factory installed, integral line voltage disconnect (non-fused) and onboard 24VAC power
  • EISA compliant motors for energy efficiency with open drip-proof design and integral thermal protection
  • Two total, MERV 8, 2" pleated, 20"x20" nominal size filters (one for each airstream)
  • UL tested flammability and smoke generation that meets NFPA 90A and 90B test standards for commercial applications
HE1XINH

Available Options

  • Fused disconnect
  • Double wall construction
  • ECM motor(s) (for best energy efficiency)
  • Motorized isolation dampers, OA, EA or both airstreams
  • Factory mounted Filter Alarms (2)
  • Independent Blower Control
HE1XINH

Accessories

FA12-G/FA12-P

  • 12" Metal Hood Type Wall Cap
  • Galvanized (G) or Paintable (P)
  • 1/4" metal screen

BD12

  • 12" Back Draft Damper
  • Mechanical "buterfly" design
  • Male/Female ends